FR 100 has been tested in accordance with EN 1366-4 and classified in accordance with EN 13501-2. A joint 10 mm wide and 5 mm deep achieves E 240 EI 240-V-X-F-W 00 to 10. A joint measuring 40 × 5 mm achieves E 240 EI 180, and a joint measuring 40 × 10 mm achieves E 240 EI 60. The specified fire resistance applies only if you adhere to the tested joint dimensions, substrates and system configuration.